HP Intelligent Power Discovery
Data sheet
HP Intelligent Power Discovery (IPD) automatically tracks new server
installation and provides higher precision, control, and automation to
power distribution. IPD helps you enhance data center capacity, while
reducing downtime and the possibility of error by human intervention.
Get the power efficiency your
business demands
HP Intelligent Power Discovery (IPD) is an energy-aware
solution which combines the advanced management
features of HP Integrated Lights-Out (iLO), HP Common
Slot Platinum Power Supplies, HP Intelligent Power
Distribution Unit (iPDU), and HP Insight Control power
management software to help you automatically track
installation of new servers into the rack and map them
to individual outlets on the iPDU.
•
Effectively measures standby power
to detect when a server is plugged in and not just
when powered on.
Information:
Sensitivity:
•
Easily identifies available power
capacity to add more servers.
Greater flexibility
Mounting:
•
Mountable in 1U or zero U spaces to
save valuable rack space. Flexible mounting of
extension bars eases cable management.
•
Uses the HP Intelligent PDU and
the Intelligent Extension Bars to reduce cabling.
Architecture:
Using power line communication technology,
HP ProLiant G6 and G7 servers
1
and Common Slot
Platinum Power Supplies now provide identification
information such as server name, UUID number, and
IP address to the Intelligent PDU and HP Insight Control
power management software. This helps reduce the time
needed to configure power distribution and management
software. What’s more, IPD intuitively detects redundant
power supplies and makes sure they are running on
different PDUs. This helps reduce unscheduled down time
and the possibility of human error.
•
Displays power consumption for
the core, stick, and outlet levels at the rack or
remotely from standard Web browsers.
Monitoring:
•
Remotely control power per outlet or even
per pair of outlets for redundantly powered equipment.
Power efficiency:
Control:
•
Range of wattage levels—460W,
750W, and 1200W—enabling you to “right-size”
your power needs with Platinum-certified (94 percent
efficient) power supplies.
Superior protection
Six load segment breakers:
Key features and benefits
With IPD your data center gets:
•
Individual breakers for
each load segment prevent a problem in one segment
from causing a power outage on the entire PDU.
Event alerts:
Precision in power-monitoring
Topology:
•
SNMP and email alerts notify operators
of impending issues that could cause a power outage.
Lock-out outlets:
•
Automatically detects and maps servers
to specific power outlets for balanced power usage.
Accuracy:
•
Locking-out individual outlets
prevents unauthorized equipment from overloading
PDUs or circuits.
Automatic redundancy checking:
•
Effectively measures power usage to
all outlets.
Data collection:
•
Efficiently gathers information from
all monitoring points at half-second intervals to make
sure that the latest data is collected.
•
Automatically
detects power configuration errors and notifies IT
administrators/operators.
3-year warranty:
•
Comes with a 3-year warranty
that safeguards your IT investment and lets you make
the most of it.
1
To review server-specific quick specs and check for power supply
compatibility, visit:
http://h18004.www1.hp.com/products/servers/
rackandpower/powersupplies/ipd/index.html
Operating efficiencies of HP common-slot power supplies
Percent of efficiency
80 PLUS
Certification
Power supply type
@ 20% load
@ 50% load
@ 100% load
460-watt (AC)
92.44%
94.64%
93.67%
Platinum
750-watt (AC)
93.36%
94.53%
93.03%
Platinum
1200-watt (AC)
92.53%
94.34%
93.21%
Platinum
Ease-of
Installation:
HP Services
•
Compatible with industry-standard
racks. Power supplies utilize the HP Common Slot
form factor that supports tool-less, hot-swap removal
and installation.
Configuration:
When technology works, business works
The challenge of virtually every IT organization is similar: To develop
and maintain an agile, efficient server infrastructure that delivers the
service levels your business needs.
•
Simply assign an IP address to the
PDU and it’s ready to use.
Integration:
HP Technology Services offer a comprehensive portfolio of HP Care
Pack Services to help design, deploy, manage, and support your IT
environment, enabling cost-effective upgrades to standard warranty
with easy-to-buy, easy-to-use support packages.
•
Gets automatically detected by HP
Systems Insight Manager (SIM) and Insight Control
power management power management software.
Multiple account levels:
Rack option hardware support
HP Care Pack services support rack-mounted HP ProLiant DL servers,
storage products, and all HP-branded rack hardware options
that qualify for inclusion with your server at the time of or after
purchase. Additionally, 22-inch and smaller external monitors, power
distribution units, and uninterruptible power supply (UPS) options up
to 12 kVA are covered under the same service level as the server for
up to 3-years from the date of purchase at no additional cost.
•
Users can be assigned full
or restricted access levels as needed.
HP Common Slot (CS) Platinum Power
Supplies
HP offers three Platinum-certified CS power supplies
that incorporate power line communication technology.
These power supplies are available in a range of
wattage levels: 460W, 750W, and 1200W.
For more information, visit:
www.hp.com/services/proliantservices
or
www.hp.com/go/proliant/carepack
HP CS Platinum power supplies are rated as the most
efficient in the industry with a power efficiency of at
least 94 percent
2
at a 40 percent load. This efficiency
level is the highest rating recognized by 80 PLUS and
EPRI. All three power supplies are Platinum certified
through the ECOS/80 PLUS certification program.
2
94 percent power efficiency, the highest rating recognized by 80 PLUS:
The 80 PLUS certification is an incentive program funded by electric utilities to
encourage manufacturer development and customer application of more energy-efficient power supplies. To earn 80 PLUS certification, a power supply
must be proven through independent testing to be 80 percent (or greater) energy efficient when delivering 20, 50, and 100 percent of the rated load
capacity with a true power factor of 0.9 or greater. For more information on the 80 PLUS program, visit:
www.80plus.org
2
HP CS Platinum Power Supplies
HP 460W CS Platinum Power Supply Kit
Input Voltage Range (Vrms)
100 to 240
Frequency Range (Nominal) (Hz)
50/60
Nominal Input Voltage (Vrms)
100
120
200
208
220
230
240
Maximum Rated Output Wattage
Rating
460
460
460
460
460
460
460
Nominal Input Current (A rms)
5.3
4.3
2.5
2.4
2.3
2.2
2.1
Maximum Rated Input Wattage
Rating (Watts)
512
505
493
493
492
492
491
Maximum Rated VA (Volt-Amp)
526
518
506
506
505
505
504
Efficiency (%)
89.8
91.2
93.2
93.3
93.5
93.6
93.6
Power Factor
0.985
Leakage Current (mA)
0.42
0.50
0.83
0.87
0.92
0.96
1.00
Maximum Inrush Current (A peak)
30
Maximum Inrush Current
duration (mS)
20
Maximum British Thermal Unit
Rating (BTU-Hr)
1747
1722
1683
1682
1679
1678
1677
HP 750W CS Platinum Power Supply Kit
Input Voltage Range (Vrms)
100 to 240
Frequency Range (Nominal) (Hz)
50/60
Nominal Input Voltage (Vrms)
100
120
200
208
220
230
240
Maximum Rated Output Wattage
Rating
750
750
750
750
750
750
750
Nominal Input Current (A rms)
8.6
7.1
4.2
4.0
3.8
3.6
3.4
Maximum Rated Input Wattage
Rating (Watts)
841
828
809
808
807
806
805
Maximum Rated VA (Volt-Amp)
863
850
830
829
828
827
826
Efficiency (%)
89.2
90.6
92.7
92.8
93
93.1
93.2
Power Factor
0.985
Leakage Current (mA)
0.42
0.50
0.83
0.87
0.92
0.96
1.00
Maximum Inrush Current (A peak)
30
Maximum Inrush Current
duration (mS)
20
Maximum British Thermal Unit
Rating (BTU-Hr)
2868
2825
2761
2757
2753
2749
2747
HP 1200W CS Platinum Power Supply Kit
Input Voltage Range (Vrms)
100 to 240
Frequency Range (Nominal) (Hz)
50/60
Nominal Input Voltage (Vrms)
100
120
200
208
220
230
240
Maximum Rated Output Wattage
Rating
800
900
120 0
120 0
120 0
120 0
120 0
Nominal Input Current (A rms)
9.3
8.6
6.7
6.5
6.1
5.8
5.6
Maximum Rated Input Wattage
Rating (Watts)
889
989
1290
1290
1290
1290
1290
Maximum Rated VA (Volt-Amp)
927
1031
1345
1345
1345
1345
1345
Efficiency (%)
90
91
93
93
93
93
93
Power Factor
0.97
Leakage Current (mA)
0.42
0.50
0.83
0.87
0.92
0.96
1.00
Maximum Inrush Current (A peak)
30
Maximum Inrush Current
duration (mS)
10
Maximum British Thermal Unit
Rating (BTU-Hr)
3033
3375
4403
4403
4403
4403
4403
3
HP Intelligent Power Distribution
Unit (iPDU)
Based on the modular PDU’s flexible core and stick
design, the iPDU offers you a new level of remote
power monitoring and control in your data center.
Integrated remote management in the iPDU core
provides high-precision monitoring of current, voltage,
wattage, and power that is 99 percent
2
accurate across
all six IEC C19 outlets. Intelligent Extension Bars plug
into the core and have five individually monitored IEC
C13 outlets. Each of these outlets can also be remotely
managed through common Web browsers.
With Insight Control power management software you
can deploy new ProLiant servers quickly and reliably;
catalog your environment accurately; proactively
monitor server health to identify possible failures
before they cause downtime; manage servers remotely
from any location; and improve power usage.
With Insight Control power management software
you can:
Measure power usage for groups of servers, helping
•
you assess how many servers can be deployed per rack
Enhance energy efficiency of the servers
•
•
Cap power usage to fit more servers within your
existing power envelope
Ensure critical services stay up during power and
The iPDU and the iPDU Intelligent Extension Bars
are key components of the IPD. Backed by the iPDU
Intelligent Extension Bars, IPD automatically discovers
ProLiant servers powered by Common Slot Platinum
Power Supplies, maps them to individual outlets on
the Intelligent Extension Bars, and records server asset
information on the iPDU and on the Insight Control
power management software. This saves you hours of
configuration time and helps you reduce errors.
•
cooling failures by reducing power to non-critical
servers
HP Insight Control power management software
integrates seamlessly with IPD to automatically
discover your power topology, lets you know exactly
how much power is needed, and gives you the ability
to take control of your IT environment.
HP Insight Control power
management software
HP servers are designed from the ground-up to be
among the best-managed servers in the industry.
HP servers with Insight Control enable you to simplify
day-to-day operations and make the most of every
dollar you spend on server assets, staff, energy, and
the facilities infrastructure.
HP Financial Services
HP Financial Services provides innovative financing
and financial asset management programs to help
you cost-effectively acquire, manage, and ultimately
retire your HP solutions. For more information on these
services, please contact your HP sales representative
or visit:
www.hp.com/go/hpfinancialservices
2
HP Performance Engineering Team, 2010 benchmark.
To better understand how HP Intelligent Power Discovery (IPD) can work for your data center, visit:
www.hp.com/go/ipd
Share with colleagues
Get connected
www.hp.com/go/getconnected
Current HP driver, support, and security alerts
delivered directly to your desktop
© Copyright 2010 Hewlett-Packard Development Company, L.P. The information contained herein is subject to change without notice. The only
warranties for HP products and services are set forth in the express warranty statements accompanying such products and services. Nothing herein
should be construed as constituting an additional warranty. HP shall not be liable for technical or editorial errors or omissions contained herein.
4AA1-5669ENW, Created June 2010
Plik z chomika:
JolanPOL
Inne pliki z tego folderu:
DL+165+G7.pdf
(217 KB)
DL580G7-4AA0-6315ENW.pdf
(223 KB)
Repozytorium ProLiant Service pack.pdf
(4747 KB)
6GB SAS Family Guide 4AA0-0612ENW.pdf
(205 KB)
DL360G7_4AA0-6314ENW.pdf
(397 KB)
Inne foldery tego chomika:
AMD
Backup
Backup diagrams
Biblioteki MSL
BladePower_Sizer
Zgłoś jeśli
naruszono regulamin