airconwarehouse.com - TROUBLESHOOTING
10.2 ALARM CODES
If a Safety Device is activated, cutting out the compressor, the Run light on the Remote Control switch blinks
continuously and ABNML is indicated on the LCD display. The Unit Identification A* etc is shown along with
the Code Number for the Fault that has occurred.
The Code Numbers relating to each type of Fault is shown below.
Heat Pump
Fault Code
Fault
0i
Safety Device (Indoor Unit)
02
Safety Device (Outdoor Unit)
03
Transmission Indoor/Outdoor Unit
05
Phase Rotation
08
Compressor High Temperature
ii
Air Inlet Thermistor
i2
Air Outlet Thermistor
i3
Freeze Protection Thermistor
20
Compressor Thermistor
22
Ambient Air Thermistor
24
Defrost Thermistor
25
Condensing Temperature Thermistor
38
PCB Protection Circuit
4i
Overload Operation for Cooling
42
Overload Operation for Heating
The LED’s 1-4 on the Outdoor Unit PCB will also light up according to the following table to indicate the fault
which has occurred.
Fault Code
LED1
LED2
LED3
LED4
Normal
-
-
-
-
0i
-
-
-
*
02
-
-
-
*
03
-
-
-
*
05
-
-
-
*
08
-
*
*
*
20
-
-
*
*
22
-
-
*
*
24
-
-
*
*
38
-
-
*
*
4i
-
-
*
*
42
-
*
*
*
ii-i3
*
*
*
*
Cooling Only
Fault Code
Fault
02
Safety Device (Indoor or Outdoor Unit)
ii
Air Inlet Thermistor
i3
Freeze Protection Thermistor
38
PCB Protection Circuit
The reason for the failure should be traced and rectified as early as possible. The unit may then be restarted
by pressing the Run/Stop button.