0153.pdf
(
6612 KB
)
Pobierz
209295613 UNPDF
Prof. Jan OLEK,
olek@purdue.edu
Mateusz RADLIŃSKI,
matrad@purdue.edu
Maria DEL MAR ARRIBAS,
marribas@purdue.edu
School of Civil Engineering, Purdue University, 550 Stadium Mall Dr., West Lafayette, 47907
IN, U.S.A
PREMATURE DETERIORATION OF JOINTS IN SELECTED INDIANA
PORTLAND CEMENT CONCRETE PAVEMENTS
PRZEDWCZESNE ZNISZCZENIE SZCZELIN DYLATACYJNYCH
BETONOWYCH NAWIERZCHNI W STANIE INDIANA
Abstract
In the last decade, the progressive deterioration of relatively new portland cement concrete
pavements was observed in several locations in Indiana. This deterioration took a form of cracking and spalling
localized in the upper part of the pavement, typically around the bottom of the saw cut groove. In order to
investigate the cause of this deterioration, 36 of 150-mm diameter cores were extracted from four different
pavements. Although the obtained specimens were subjected to various tests, this paper only contains the results of
air void system analysis, as the ultimate mode of failure appeared to be freeze-thaw related. The results indicate that
even though some of these concretes might have had satisfactory air-void system at the time of placement, its
effectiveness became compromised over time by combined effects of water and salt ingress (formation of ettringite
and Friedel’s salt).
Streszczenie
W ciągu ostanich kilkunastu lat w stanie Indiana (USA) zaobserwowano postępujące zniszczenie
stosunkowo nowych nawierzchni betonowych. Przedwczesne zniszczenia w postaci pęknięć i wykruszeń
wystepowaly wokół podluŜnych i poprzecznych szczelin dylatacyjnych (w górnej części nawierzchni, na dnie
nacięcia dylatacyjnego). W celu zbadania przyczyn występujących zniszczeń wykonano 36 odwiertow, z których
pobrano walce o średnicy 150 mm do badań laboratoryjnych. Próbki zostały wycięte z czterech róŜnych odcinkow
drogowych. ChociaŜ pobrane walce poddano kilkunastu testom, w artykule przedstawiono wyniki jednego z
oznaczen. Analiza systemu pustek powietrznych w stwardniałym betonie wskazuje, Ŝe przyczyną przedwczesnego
zniszczenia nawierzchni było częściowe wypełnienie pustek powietrznych etryngitem lub solą Friedela. Obecność
tych związków wskazuje na duŜy stopień akumulacji soli odladzających i zawilgocenia betonu w obrębie nacięć
spowodowany brakiem zdolności dylatacji do odprowadzania wody.
1. Introduction
Some of the 5-10 years-old concrete pavements located in various part of Indiana, USA, that
otherwise perform well, show signs of premature deterioration (in the form of excessive cracking
and spalling) primarily in areas near the longitudinal joints; in several cases, the transverse joints
areas have been affected as well. The deterioration has been observed (among others) at SR 933
near South Bend, on some sections of I-65, as well as on several roads in the Indianapolis area
859
(i.e. 86th and Payne Rd). Some of the typical examples of the distress observed are presented in
Figure 1.
Fig. 1. Section of pavement on W 86
th
Street, Indianapolis, IN (left) and SR 933 near South Bend, IN (right)
This paper contains the results of air-void system analysis (using ASTM C 457) performed on
number of cores extracted from the following locations:
·
“on” ramp from US 67 to east-bound I-465 located in the south-west section of
Indianapolis, IN;
W 86
th
Street (near Michigan Road) located in the north section of Indianapolis, IN;
· SB I-65 (near MLK Street exit) in Indianapolis, IN
· SR 933 near South Bend, IN (section between Darden Road and Willow Street).
The cores obtained from the W 86th Street were actually removed from two locations along
the eastbound lane. The first location was immediately to the west of the intersection of W 86
th
Street with N. Payne Road and it is referred to in this paper as “before lights” (BL) location.
This section of the pavement was in good condition, with no visible signs of distress. The
second location was immediately to the east of the intersection and it is referred to in this paper
as “after lights” (AL) location. The condition of the pavement at this location was considerably
worse than that to the west of the intersection, with severe to moderate deterioration observed in
both longitudinal and transverse joints (see left side of Figure 1). Due to the significant
differences in the pavement conditions for the BL and AL locations, the test results obtained
from these two sections were analyzed separately.
·
2. Collection of cores
When selecting the coring locations on the ramp from US 67 to eastbound I-465E and on W
86
th
Street an attempt was made to obtain specimens for various cases presented in Figure 2 and
listed below:
A – damaged area of the transverse joint
B – damaged area of the longitudinal joint near the junction of the longitudinal and transverse
joints
C – damaged area of the longitudinal joint away from the transverse joint
860
D – mid-span of the slab, undamaged section
E – undamaged transverse joint adjacent to the damaged transverse joint
Fig. 2. Proposed coring locations
3. Preparation of test specimens
3.1 Sampling and testing procedure
A number of specimens needed for various types of tests were prepared by dissecting each of
the collected cores as shown in Figure 3. The specimen for air-void system analysis (shown
hatched), had planar dimensions of 110×110 mm and was generally collected from the top
section of the core. In four instances, the damage to the cores removed from the joints was so
extensive that it was not possible to obtain the specimens directly from the top section of the
core. As a result, these specimens were obtained from the lower portion of the core.
System Analysis
Air-Void
System Analysis
XRD and SEM
Chloride
Concentration
RCP and
Sorptivity
2 X F-T
2 X F-T
RCP and
Sorptivity
Fig. 3. Schematic of test specimen locations within each core
3.2 Polishing of specimens for air-void system analysis
All the specimens for air-void system analysis were polished using automatic lapping wheel,
following the procedures of ASTM C 457 [1].
861
3.3 Testing procedure
The air-void system analysis was conducted using modified point-count method following
ASTM C 457 [1]. The test was performed in such way that the results were recorded for each
line (traverse) separately, which allowed for determination of the distribution of air voids with
depth of the core (the results for every four lines were averaged to increase the accuracy). In
addition, distinction was made between the entrained and entrapped voids. The selection of
entrapped voids, although arbitrarily, was based on the size (larger than about 1 mm), shape
(irregular rather than round) and location (mostly adjacent to at least one particle of aggregate).
Finally, it should be pointed out that voids in-filled with secondary products were not counted
(regardless of whether they appeared to be entrapped or entrained) as such voids do not
contribute to the freeze-thaw resistance of concrete.
4. Test results
The summary of all test results obtained during the ASTM C 457 analysis is presented in
Table 2. Additionally, the average values and standard deviations for all the relevant air-void
system parameters (total air content, entrained air content, void frequency and spacing factor)
were calculated separately for the group of undamaged and damaged cores at each location.
These results are presented in Figures 4-7.
For reference, provided below are the approximate recommended values of parameters of air-
void system for freeze-thaw resistant air-entrained concrete [2, 3]:
air content: 6.5% (by volume of concrete);
void frequency: > 1.5 times the air content;
specific surface area: 23.6 mm
2
/mm
3
;
spacing factor: 0.20 mm.
5. Analysis and discussion
As seen in Table 2, for the group of cores obtained from the US 67 ramp, the air content (both
total and entrained) was highest for cores 5F and 9D (5.5 – 6.0%). The air content in all other
cores was about 4% or less, which is significantly lower than 6.5% typically specified for PCC
pavements exposed to freezing and thawing [2,3]. The lowest entrained air content was obtained
for cores 6D and 8A (2.0 - 2.4%). Accordingly, these two cores exhibited the highest values of
spacing factor (0.52 mm and 0.62 mm, respectively), which is considerably above 0.20 mm
considered to be indicative of frost-resistant concrete [2,3]. Both damaged cores (1A and 8A)
had relatively high spacing factor (0.39 mm and 0.62 mm, respectively).
All cores from W 86
th
Street BL location had relatively uniform amount of entrained air (in
the range of about 3.0 - 5.0%). However, the values of spacing factor for these specimens were
found to be very low (0.11 mm to 0.16 mm), which is below recommended value of 0.20 mm. It
should be also noted that the values of both void frequency and specific surface (although these
are not independent variables) are very high for all cores from W 86
th
Street BL (Table 2). Thus,
the good parameters of air-void system of cores collected from that location appear to explain the
lack of damage observable at the joints.
862
Table. 2. Summary of test results from air-void system analysis
All cores obtained from W 86
th
Street AL location had relatively low entrained air content
varying from 2.5% (cores 2D and 4D) to 4.7% (core 10E). The cores from this location also
exhibited high scatter in the spacing factor, with values ranging from 0.20 mm (core 3D) to 0.63
mm (core 7A). It can also be noticed that for all damaged cores (7A, 8B, 9F
*
and 11C) the
measured spacing factor was 0.39 mm or higher.
The entrained air content of all three cores obtained from SR 933 was about 4.0%. The
spacing factor for the cores from mid-span of the slab was 0.41 mm (core 0D) and 0.23 mm
(core 1D). The core obtained from the undamaged transverse joint (2E) had a value of spacing
factor of 0.28.
*
Core 9F appeared to be undamaged (no surface damage) but was deteriorated beneath the surface
863
Plik z chomika:
everesta
Inne pliki z tego folderu:
0129.pdf
(654 KB)
0009.pdf
(1568 KB)
0030.pdf
(3777 KB)
0042.pdf
(1238 KB)
0069.pdf
(412 KB)
Inne foldery tego chomika:
! PROGRAMY ANDROID 2017
! ♥ GIFY-PIĘKNE ♥
!!!gify dzieci
!!!GIFY LINIE
!!!Kościół Publikacje
Zgłoś jeśli
naruszono regulamin