mg90e102.PM6
Profibus DP V1
About this Document .............................................. 2
Profibus DPV1 introduction .................................... 3
Principle of data exchange by Profibus DPV1 ...... 4
Addressing scheme for DP V1. ............................... 5
Accessing VLT parameters on DP V1. ................... 5
Description of DP V1 Read / Write Telegram. ....... 7
Function of Profidrive parameter channel. ......... 10
DP V1 on PLC based master.
(Master class 1) ....................................................... 16
DP V1 on Configuration / commissioning tools.
(Master class 2) ....................................................... 16
Examples Profidrive Parameter access Services. . 30
Example of DP V1 Read Parameter Service. ....... 35
Data types. .............................................................. 37
Size Attributes. ....................................................... 38
MG.90.E1.02 - VLT is a registered Danfoss trademark
1
Profibus DP V1
About this Document
This document describes the features supported of
the Profibus DP V1 functions in all Danfoss Drives
with a Profibus option.The functionality is described
at a level, which will be sufficient for most system
configuration and managing activities.
It is assumed, that the following Specifications /
limitations are fully respected:
Profidrive Profile V 2 specifications.
Profidrive Profile V3 specifications concerning
the DP V1 Profidrive parameter channel.
Limitations in DP V1 features supported
Beside the drive behavior, a brief description of
master applications of master class 1 and master
class 2 can be found.
What you should already know
The Danfoss Profibus is designed to communicate
with any master abiding by the Profibus DP
standard.
For full system overview, please refer to the following
documents:
Operating Manual for FCM300 (ordering no.
MG03BXYY), FCD300 (ordering no.MG04BXYY),
VLT2800 (ordering no. MG28AXYY)
It is therefore assumed, that you have full
knowledge of the PC or PLC you intend to use as a
master in your system. Any questions pertaining
non-Danfoss hardware or software products is
beyond the scope of this manual, and is no concern
to Danfoss.
Profibus Manual for FCM300, FCD300,
VLT2800 (ordering no. MG90AXYY)
where
X
is referring to the version number code and
YY
the language code.
For non-Danfoss equipment, please refer to the
appropriate specifications.
If you have questions about how to set up Master –
Master connection or communication to non-
Danfoss slaves, the appropriate manuals should be
consulted.
For further detailed description of this matter, the
following documents might be useful:
Technical Guide “PROFIBUS – DP Extensions to
EN 50170 (DPV1)” V2.0, April 1998, Order no.
2.082
Software versions
The following table shows from which software ver-
sions Profibus DPV1 is supported. The software ver-
sion can be read-out in parameter 624
Software
versions.
Draft PROFIBUS Profile PROFIdrive Profile Drive
Technology V3.0 September 2000, Order no.
3.172
Unit
Software version
FCD 300
Ver. 1.30 / 2.00
Even if you are an experienced Profibus system
builder, we suggest you to read this Guide in its
entirety before you start programming, since
important information can be found in all chapters.
VLT 2800
Ver. 2.62 / 2.00
VLT 5000
Ver. 3.61 / 4.00
Assumptions
This guide assumes, that you are using a Danfoss
frequency converter with Profibus DP V1
functionality. It is also assumed, that you as a
master are using a PLC and/or PC equipped with a
Communication card supporting all the Profibus
communication services required by your
application.
2
MG.90.E1.02 - VLT is a registered Danfoss trademark
Profibus DP specifications.
Profibus DP V1
Profibus DPV1 introduction
The Profibus DP extension DPV1 offers additional to
the cyclical data communication of DP V0, an a-
cyclical communication. This feature is possible by a
DP master class1 (e.g. PLC) , as well as a DP
master class 2 (e.g. PC Tool).
Cyclical communication means that data transfer
takes place all the time with a certain update rate.
This is the known DP V0 function normally used for
quick update of I/O Process Data.
A-cyclical communication means a one time event,
mainly used for Read / Write on parameters from
Process controllers, PC based tools or monitoring
systems.
Features of a Master class 1 system:
Features of a Master class 2 system:
Initiate / Abort a-cyclical connection.
A-cyclical read/write on parameters.
A-cyclical read/write on parameters.
The a-cyclical connection is fixed , and can not be
changed during operation.
The a-cyclical connection can dynamically be
established (Initiate) or removed (Abort) even though
a master class 1 is active on the network.
In general a master class 1 is used as Process
controller, responsible for commands, speed
reference, status of the application etc ( PLC or PC
based controller.)
The MC 2 a-cyclical connection is typically used for
configuration or commissioning tools for easy access
to each parameter in any slave in the system.
The MC 1 a-cyclical connection might be used for
general parameter access in the slaves.
The frequency converter supports a subset of the V1 specifications shown in the table below.
Type of
Master
Read
Write
Data
Initiate
Abort
Alarm
Danfoss
type
transport
Frequency
(read data) (read data)
(read and
(open a
(close a
converter
from slave) to slave)
write data) connection) connection)
FCD 300, VLT2800 MC 1
OK
OK
-
-
-
-
FCM 300
MC 2
OK
OK
-
OK
OK
-
VLT5000, VLT6000 MC 1
OK
OK
-
-
-
-
VLT8000 AQUA
MC 2
OK
OK
OK
OK
OK
-
MG.90.E1.02 - VLT is a registered Danfoss trademark
3
Cyclical data exchange (DP V0).
Profibus DP V1
Principle of data exchange by Profibus DPV1
In a DP cycle the MC 1 will first update the cyclical
process data for all slaves in the system. After that
the MC 1 has the possibility of sending one a-
cyclical message to one slave. If a MC 2 is
connected, the MC 1 will handle over the Token to
MC 2 who now is aloud to send one a-cyclical
message to one slave. After that, the token is
handled back to the MC 1, and a new DP cycle is
started
MC : Master Class
C1...Cn: Cyclical data
AC1: Acyclical data Master Class 1
AC2: Acyclical data Master Class 2
A DP V1 Read/Write service takes place via a
Profibus SD2 telegram, which is a telegram of
variable length as shown on the figure below.
SD
LE
LEr
SD
DA
SA
FC
DSAP SSAP DU
FC ED
S
68H
x
X
68H
xx
xx
x
xx
xx
x...
xx
16H
SD
Start Delimiter
LE
Length
Ler
Length repeat
DA
Destination Address
SA
Source Address
FC
Function Code
DSAP
Destination Service Access Point
SSAP
Source Service Access Point
DU
Data Unit for DP services
FCS
Frame Checking Sequence
ED
End Delimiter
4
MG.90.E1.02 - VLT is a registered Danfoss trademark
Profibus DP V1
Profibus DP services is activated via specific Service
Access Point’s (SAP). For a-cyclical communication,
the following SAP are specified:
Master SAP
Slave SAP
Meaning
50 (32H)
49 (31H)
Master Class 2: Initiate request
50 (32H)
0..48 (0..30H)
Master Class 2: Abort, Read, Write, Data transfer
51 (33H)
50, 51 (32H, 33H) Master Class 1: Alarm
51 (33H)
51
Master Class 1: Read, Write
Addressing scheme for DP V1
The structure of a DP V1 slave is shown
in the figure.
A DP V1 slave consists of a number of
physical or virtual slots. Slot 0 is always
present, and represents the basic unit.
Each slot can contain until 255 data blocks
addressed by an index and of until 255 byte
length.
The master must address a variable in the
DP V1 slave as follows:
/Slave address/Module #/Index #
Accessing VLT parameters on DP V1
This section describes how DP V1 can be used for
accessing VLT parameters.
A Danfoss DP V1 slave only contains Slot 0.
Because of the complex parameter structure of
drives, a specific procedure for accessing
parameters for drives is defined. This is named the
“Profidrive Parameter Channel”, and is part of the
Profidrive Profile V3 specifications.
According to this, parameter access must be made
trough one single DP V1 object with the following
address:
Slot = 0.
Index = 47.
MG.90.E1.02 - VLT is a registered Danfoss trademark
5
Plik z chomika:
motmotg